Dawlance AC Error Codes

AC BrandsDawlance
Error CodeMalfunction
E0 Water pump malfunction
E1High pressure protection of compressor
E2Indoor anti-frozen protection
E3Low pressure protection of compressor
E4Air discharge high-temperature protection of compressor
E5Overload protection of compressor or Inverter error
E6Communication malfunction
E8Indoor fan protection
E9Water flow protection
F0Malfunction of indoor environment sensor at air return vent
F1Evaporator sensor malfunction
F2Condenser sensor malfunction
F3Outdoor environment sensor malfunction
F4Malfunction of air discharge sensor
F5Malfunction of environment sensor on displayer
EHAuxiliary electric heater malfunction

2 . Troubleshooting for Typical Faults
Troubleshooting sequence: Firstly, view the error description according to the error code on the
display. If E5 is displayed, it is needed to open the electric box of outdoor unit and record the LED
indication on the outdoor main control board. Then, find out the fault by referring to the LED
Indication Codes of Outdoor Main Control Board. After confirming the fault, find the cause
according to the instructions below:

A. Communication Fault (E6)
Check the communication wire between indoor unit and outdoor unit to ensure if the wire is
open circuited or short circuited and if the connector is loose.

B. Temperature Sensor Fault (F0, F1, F2, F3, F4 and F5)
Check if the wire from temperature sensor to mainboard is loose. Insert tightly if loose. If the
temperature sensor does not loosen from the mainboard, pull off the temperature sensor and
use multimeter to measure the resistance on the two ends of temperature sensor. If the
resistance is infinite high or very low (close to “0”), we can judge that the sensor is damaged
and shall be replaced. For the position of each temperature sensor on mainboard, please see
the PBC interface diagram attached.

C. High Pressure Protection
When high pressure protection is detected for 3 seconds successively, the unit will shut down
all the loads (except the 4-way valve of heating) and shield all the keys and remote signals
except the On/Off, in which case the run indicator will blink (or display fault code E1) and the
buzzer will alarm. The fault cannot be restored automatically. You shall need to press ON/Off
to stop the unit, then turn off the indicator (or clear E1 display) before pressing ON/OFF. The
unit will be restarted if the high pressure protection disappears. Otherwise, the run indicator
will blink (or display fault code E1) and the buzzer will alarm.

D. Low Pressure Protection
It will be deemed low-pressure protection as long as it is detected for 30 seconds
successively that the low-pressure switch is cut off, in which case the indicator will blink (or
display E3), all the loads will be stopped (except the 4-way valve of heating). If the fault is
eliminated, the compressor will be restarted after 3 minutes. If three low-pressure faults of
compressor are detected successively in 30 minutes from the first detection to the occurrence
of fault, the indicator will blink (or display E3) and the buzzer will alarm. The unit cannot be
restored automatically. You shall need to pre ss ON/Off to stop the unit, then turn off the
indicator before pressing ON/OFF. The unit will be restarted if the high pressure protection
disappears. Otherwise, the run indicator will blink (or display fault code E3) and the buzzer
will alarm.

E. Exhaust Over temperature Protection
After the compressor is started, it is detected for 30 seconds successively that the exhaust
temperature is higher than 115¥ ; E4 is displayed; and all the loads will be stopped (except
the 4-way valve of heating). After the compressor is stopped for 3 minutes, the fault code will
be cleared and the complete unit will resume to operation if the exhaust temperature is lower
than 90¥ . If such protection occurs three time successively within 30 minutes, the complete
unit cannot resume to operation, in which case E4 will be displayed and the buzzer will alarm.
You shall need to press ON/Off to stop the unit and then press ON/OFF again. If the exhaust
temperature is lower than 90¥ , the unit will run under preset mode.

F. Communication Fault between Main Controller and Inverter
Check if the communication wire between main control board and inverter is loose or broken.

G. E5 Protection (Overcurrent Protection or Inverter Fault)
Firstly, please check if the overload switch of the compressor is open. If it is not open or the
compressor has no overload switch, please refer to the troubleshooting process for inverter.
3. Inverter Troubleshooting
3.1 Typical Troubleshooting for Inverter GUHD09NK3AO, GUHD12NK3AO and GUHD18NK3AO
3.1.1 Troubleshooting and Treatment of Inverter Faults
(1) DC Overvoltage: If it is detected that the DV voltage is higher than 420V upon energization,
this fault will be alarmed. It is non-restorable if this protection occurs six times successively in
1 hour. In this case, you must de-energize, discharge completely and re-energize before you
can eliminate this fault.
(2) DC Undervoltage: If it is detected that the DV voltage is lower than 200V upon energization,
this fault will be alarmed. It is non-restorable if this protection occurs six times successively in
1 hour. In this case, you must de-energize, discharge completely and re-energize before you
can eliminate this fault.
(3) Inverter Module Resetting: Initialize the inverter program. This fault is alarmed upon
energization after each de-energization or upon resetting of inverter chip caused by some
interference. 5s will be displayed after occurrence of this fault. Note: It is normal that this
alarm will occur upon energization after de-energization.
(4) Inverter IPM Abnormal: This fault is alarmed when it is detected that IMP module or PFC
module is abnormal. It is non-restorable if this protection occurs six times successively in 1
hour. In this case, you must de-energize, discharge completely and re-energize before you
can eliminate this fault.
(5) Radiator Fin Overheat Protection: This fault is alarmed when it is detected in 1s successively
that the radiator fin temperature is higher than 105¥ . It is non-restorable if this protection
occurs six times successively in 1 hour. In this case, you must de-energize, discharge
completely and re-energize before you can eliminate this fault.
(6) Compressor Overcurrent Protection: This fault is alarmed when it is detected in 1ms
successively that the transient current of compressor is higher than 18A. It is non-restorable if
this protection occurs six times successively in 1 hour. In this case, you must de-energize,
discharge completely and re-energize before you can eliminate this fault.
(7) Compressor in Loss of Synchronization: This fault is alarmed when it is detected in 2s
successively that the negative potential of the compressor in run period is lower than 20V. It is
non-restorable if this protection occurs six times successively in 1 hour. In this case, you must
de-energize, discharge completely and re-energize before you can eliminate this fault.
(8) Compressor Over-frequency Protection: This fault is alarmed when it is detected in 2s
successively that the working frequency of compressor is higher than 200HZ or the difference
between working frequency and preset frequency is over 40Hz. It is non-restorable if this
protection occurs six times successively in 1 hour. In this case, you must de-energize,
discharge completely and re-energize before you can eliminate this fault.
(9) Communication Fault between Inverter and Main Controller: This fault is alarmed when it is
detected in 60s successively that it cannot communicate with the main controller normally.
This fault can be restored automatically.
(10) Current Detection Circuit Fault: This fault is alarmed when it is detected that the average bias
voltage is higher than 12.5% of 1.65V. It is non-restorable if this protection occurs six times
successively in 1 hour. In this case, you must de-energize, discharge completely and
re-energize before you can eliminate this fault.
3.1.2 Troubleshooting for Typical Inverter Faults
3.1.2.1 Switch Power Module is damaged.
The reasons that might cause damage to switch power module include:

  • Input DC voltage is too high, over 430V
  • High-frequency transformer is damaged.
  • The IC card for switch power control is damaged.
  • The loads short circuit the 12V indicator.

 

3.1.2.2 IPM Module Protection
The possible reasons causing inverter IPM protection include:
z The screws fixing the IPM module or PFC module is not properly tightened.
z The IPM module or PFC module is damaged.
z The IPM module or PFC module is in poor radiation.
z The compressor is abnormal or the compressor wiring is wrong.
z The current test resistor R30, R31 or R44 is damaged.
z Interference.

21 Comments. Leave new

  • nice information really like it.

    Reply
  • Great content! Super high-quality! Keep it up! 🙂

    Reply
  • Please solve my problem my inverter split ac dawlence elegence not working then power on f1 error show on the display please help me

    Reply
  • Where is temperature sensor located in indoor

    Reply
    • Open your top cover of AC ..behind the cleaning filters temperature sensor is located..

      Reply
  • In point B you mentioned PBC interface diagram. Where is that diagram please?

    Reply
  • Ahmed Umair
    May 13, 2020 8:57 am

    I was told by a technician that F1 error is shown when outdoor kit becomes faulty.
    Is that correct

    Reply
  • Salman Sultan Sultan ul Hassan
    May 19, 2020 9:59 pm

    How to Fix The Problem of Error H6 of Dawlance Split AC
    Model DAC-18CT3-I

    Reply
  • I’m amazed, I must say. Seldom do I come across a blog that’s both equally educative and interesting, and let me tell you, you’ve hit the nail on the
    head. The issue is something that not enough people are speaking intelligently about.

    I’m very happy that I came across this in my hunt for something relating to this.

    P.S. If you have a minute, would love your feedback on my new website
    re-design. You can find it by searching for «royal cbd» — no sweat if you can’t.

    Keep up the good work!

    Reply
  • Khanwada khan
    May 25, 2020 11:02 am

    Ec error

    Reply
  • Stevie Mcshane
    June 1, 2020 12:40 pm

    Hiya, I am really glad I have found this information. Nowadays bloggers publish only about gossip and internet stuff and this is really annoying. A good web site with interesting content, this is what I need. Thanks for making this web-site, and I’ll be visiting again. Do you do newsletters by email?

    Reply
  • Margret Mcphearson
    June 2, 2020 8:29 am

    Hiya, I am really glad I’ve found this info. Today bloggers publish only about gossip and internet stuff and this is really frustrating. A good site with interesting content, this is what I need. Thank you for making this web-site, and I will be visiting again. Do you do newsletters by email?

    Reply
  • If some one needs expert view concerning blogging afterward i recommend
    him/her to pay a quick visit this web site, Keep up
    the fastidious job.

    Look at my web page – Carter

    Reply
  • imran saeed
    July 3, 2020 10:21 am

    my dawlance invertor a.c aura 30 show F1 error please help me

    Reply
  • Heya i am for the first time here. I came across this board
    and I find It truly useful & it helped me out a lot. I’m hoping to present something again and help others like you aided me.

    Also visit my page :: Skincell Pro Australia

    Reply
  • E3 error is displayed on Dawlance inverter AC .

    Reply
  • Lester Brethour
    September 6, 2020 3:41 am

    Very nice info and straight to the point. I am not sure if this is actually the best place to ask but do you folks have any thoughts on where to employ some professional writers? Thx

    Reply
  • 只需要上網辦理手續,手續簡單,提供最貼心的方案 樓宇按揭貸款- 中國及海外業務| 中國業務| 海外業務. … 永隆銀行竭誠為您實現置業大計,提供一站式的國內樓宇按揭貸款服務,透過本行的專業服務及靈活貸款安排, …

    Reply

Leave a Reply

Your email address will not be published. Required fields are marked *

Fill out this field
Fill out this field
Please enter a valid email address.
You need to agree with the terms to proceed

You May Also Like

Starship Troopers 1997  download torrent
kenwood ac error codes
Kenwood AC Error Codes

Subscribe to our Youtube Channel

Must Read

Menu